In an RO plant, normalised feed-side pressure drop rises and permeate flux falls while salt rejection stays essentially unchanged. The most probable problem is
Aoxidative damage to the polyamide layer by chlorine
Bparticulate or biological fouling of the feed channel and membrane surface ✓
Cexcessive ozone in the permeate
Dcomplete exhaustion of the softener resin
Explanation
A rising feed-side pressure drop and falling flux with steady salt rejection point to particulate or biological fouling. Chlorine oxidation would damage the membrane and increase salt passage (lower rejection).